STATOR WINDING PROCESS
First connections are noted down and then
connections are opened. Old coils are removed one by one by means of special long chisel tool.
New coils are placed in stator after testing them in air at 2 X Un +1 Kv for 60 sec withstand capacity.
IR value is also checked and it should be greater than 100 M ohms.
coils in stator also tested for group of 3-4 coils and leakage current is noted down.
Either VPI or Press Moulding process is used for HT motor stator manufacturing